Siemens SINAMICS G110D Operating Instructions Manual page 65

Distributed converter
Hide thumbs Also See for SINAMICS G110D:
Table of Contents

Advertisement

Note
Information about installation
The rating plate data that you enter must correspond to the connection type of the motor
(star/delta), i.e. with a delta motor connection, the delta rating plate data must be entered.
In which region of the world is the motor used? - Motor standard [P0100]
● Europe ICE: 50 Hz [kW] - factory setting
● North America NEMA: 60 Hz [hp] or 60 Hz [kW]
What is the prevailing temperature where the motor is operated? [P0625]
● Motor ambient temperature [P0625], if it differs from the factory setting = 20° C.
What control mode do you want to use for your application? [P1300]
There are variety of settings for P1300; the default being 0, which is V/f with linear
characteristic. This setting is suitable for most applications. For further information, refer to
the Parameter List for the SINAMICS G110D.
What command and setpoint sources are you using?
The command and setpoint sources that are available depend on the Inverter. The
SINAMICS G110D by default uses the fieldbus interface.
● Possible command sources [P0700]
– Operator Panel
– Fieldbus (default setting for the SINAMICS G110D Inverters)
– Local digital inputs/switches
● Possible setpoint sources [P1000]
– Motorized potentiometer
– Analog setpoint
– Fixed frequency (default setting for the SINAMICS G110D Inverters)
– Fieldbus
Minimum/maximum frequency of the motor
The minimum and maximum frequency with which the motor operates or is limited
regardless of the frequency setpoint.
● Minimum frequency [P1080] - factory setting 0 Hz
● Maximum frequency [P1082] - factory setting 50 Hz
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Commissioning
5.3 Preparing for commissioning
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents