Siemens SINAMICS G110D Operating Instructions Manual page 49

Distributed converter
Hide thumbs Also See for SINAMICS G110D:
Table of Contents

Advertisement

Cable, connectors and tools specifications
The detailed specifications for the cables, connectors and tools required to manufacture the
necessary cables for the SINAMICS G110D are listed in the following tables.
Note
NFPA compatibility
These devices are intended only for installation on industrial machines in accordance with
the "Electrical Standard for Industrial Machinery" (NFPA79). Due to the nature of these
devices they may not be suitable for installation in accordance with the "National Electrical
Code" (NFPA70).
Table 4- 11
Tools
Crimp tool (Q8/0 and Q4/2)
Removal tool (Q8/0)
Removal tool (Q4/2)
No special tools are required for the Control Unit connectors
Table 4- 12
Control Unit connectors
Connector
ASI (M12 )
Digital input and Analog output (M12 )
Table 4- 13
Mains supply connector
Power
cable size
cable type
rating
0.75 kW 1.5 mm
(3+E) YY
2
16 AWG
Unscreened
1.50 kW
3.00 kW 2.5 mm
(3+E) YY
2
14 AWG
Unscreened
4.00 kW
5.50 kW 4 mm
(3+E) YY
2
12 or 10
Unscreened
7.50 kW
AWG
4 x crimps are required for each inverter; use 75°C copper wire only
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Binder part numbers
Straight connector
99-0436-14-05
99-0437-14-05
All connector parts are Harting Q4/2
Shell
Crimp
size
Harting Q4/2
1.5 mm
16 AWG
0912 006 3141
2.5 mm
14 AWG
4 mm
2
12 or 10
AWG
Harting part number
0999-000-0110
0999-000-0319
0999-000-0305
Right-angle connector
99-0436-24-05
99-0437-24-05
Crimp number
Hood
0932 000 6204
0912 008 0527
2
0932 000 6205
1912 008 0526
2
0932 000 6207
Connection
4.8 Cables and connections
Gland/Seal
0900 000 5059
1900 000 5190
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents