(N) Operation via communication and its settings
• The relation between the device of the programmable controller CPU and remote register (RWw, RWr) of the remote device
station is as follows: The devices used actually are indicated in shaded regions.
 Program example for reading the inverter status
The following program turns on Y00 of the output unit when station 1 inverter is running
SM1536
SD1536.0
SD1540.0
(0)
M0
X1002
(4)
(7)
One
station

These signals are initial values. You can change output signals using Pr.190 to Pr.196, Pr.313 to Pr.315 (Output terminal function
selection).
66
PARAMETER
Programmable controller CPU
For writing
W100
W101
W102
W103
W104
W105
W106
W107
W108
W109
W10A
W10B
For reading
W000
W001
W002
W003
W004
W005
W006
W007
W008
W009
W00A
W00B
X100F
Remote input
b15
b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
RXF
to
RX0
0
RX1F
to
RX10
Inverter status
b0: During forward rotation
b1: Reverse running
b2: Running (RUN)∗1
b3: Up to frequency (SU)∗1
b4: Overload alarm (OL)∗1
b5: Instantaneous power failure (IPF)∗1
b6: Frequency detection (FU)∗1
b7: Fault (ABC1)∗1
b8: ─ (ABC2)∗1
b9: ─ (DO0)∗1
b10: ─ (DO1)∗1
b11: ─ (DO2)∗1
Remote device station
(station 1)
RWw0
RWw1
RWw2
RWw3
RWr0
RWr1
RWr2
RWr3
Remote device station
(station 2)
RWw0
RWw1
RWw2
RWw3
RWr0
RWr1
RWr2
RWr3
0
0
0
0
0
0
0
0
[Inverter status]
M0
Check the data link status of the station 1
Y30
Turn on the output unit (Y00)
END
X1000
0
0
0
0
0
0
0