Modbus Register; Inverter Status / Control Input Command; Operation Mode / Inverter Setting - Mitsubishi Electric A800-E Instruction Manual

Hide thumbs Also See for A800-E:
Table of Contents

Advertisement

(N) Operation via communication and its settings
MODBUS register
• The following shows the MODBUS registers for system environment variables (read/write), real time monitor items (read),
parameters (read/write), faults history data (read/write), and model information monitor items (read).
• System environment variables
Register
40002
Inverter reset
40003
Parameter clear
40004
All parameter clear
40006
Parameter clear
40007
All parameter clear
40009

Inverter status / control input command

40010

Operation mode / inverter setting

40014
Running frequency (RAM value)
40015
Running frequency (EEPROM value)

Settings in the communication parameters are not cleared.

The data is written as a control input command for writing.
The data is read as the inverter status for reading.

The data is written as an operation mode setting for writing.
The data is read as the operation mode status for reading.

The Pr.811 setting is available only for the FR-A800-E inverter.
[Inverter status / control input command]
Bit
Control input command
0
Stop command
1
Forward rotation command
2
Reverse rotation command
3
RH (High-speed command)
4
RM (Middle-speed operation command)
5
RL (Low-speed operation command)
6
JOG (JOG operation)
7
RT (Second function selection)
8
AU (Current input selection)
9
CS (Automatic restart after instantaneous power failure)
10
MRS (Output stop)

11
STP (STOP) (Start self-holding)
12
RES (Inverter reset)

13
0
14
0
15
0

The signal within parentheses ( ) is the initial status. The input signal function can be changed using Pr.180 to Pr.189 (Input terminal function
selection). JOG operation/automatic restart after instantaneous power failure/start self-holding selection/reset cannot be controlled over a
network, so in the initial status bit6, bit9, bit11, and bit12 are invalid. To use bit6, bit9, bit11, and bit12, change the signal by Pr.185, Pr.186,
Pr.188, or Pr.189.
For details of Pr.180 to Pr.189, refer to the Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter.

The inverter run enable signal is in the initial status for the separated converter type.

The signal within parentheses ( ) is the initial status. The output signal function can be changed using Pr.190 to Pr.196 (Output terminal
function selection).
For details of Pr.190 to Pr.196, refer to the Instruction Manual (Detailed) of the FR-A800/FR-F800 inverter.

No function is assigned in the initial status for the separated converter type.
[Operation mode / inverter setting]
Mode
Read value
EXT
H0000
PU
H0001
EXT JOG
H0002
PU JOG
H0003
NET
H0004
PU + EXT
H0005

Writing is available depending on the Pr.79 and Pr.340 settings. For details, refer to the Instruction Manual (Detailed) of the FR-A800/FR-F800
inverter.
The restrictions depending on the operation mode changes according to the computer link specifications.
48
PARAMETER
Definition
Read/write
Write
Write
Write
Write

Write

Read/write

Read/write

Read/write
Write







Write value
H0010

H0011

H0014
Any value
Set H965A.
Set H99AA.
Set H5A96.
Set HAA99.
Refer to the following.
Refer to the following.
The frequency indication can be changed to the indication in
rotations per minute according to the Pr.37, Pr.144, and Pr.811
settings. (Refer to the Instruction Manual (Detailed) of the FR-
A800/FR-F800 inverter.)
Definition
Inverter status
RUN (Inverter running)
During forward rotation
During reverse rotation
SU (Up to frequency)
OL (Overload)

IPF (Instantaneous power failure)
FU (Frequency detection)
ABC1 (Fault)

ABC2 (—)

Safety monitor output

0
0
0
0
0
Fault occurrence
Remarks




