Advertisement

Parameter Name
Choose wich parameter is retransmitted by the analog
Retransmit
output
Option
Description
None
Do not retransmit value
Set Point
Set point
V Output
RMS voltage output
I Output
RMS current output
Power
Average output power
DEFAULT: Power
Parameter Name
Set the value of retransmitted parameter
Retransmit
to be represented by the full scale of the
Sale
analog output. See the table below
Recommended
Retransmit
Retransmission
Scaling
Set Point
100
xV where x is the
V Output
Nominal Line
Voltage
xA where x is the
I Output
Nominal Line
Current
Power
100
Parameter Name
Retransmit Type
Choose type of signal for the retransmission output
Option
Value
0-10V
1
4-20mA
0
0-20mA
2
DEFAULT: 0-10V
1
Parameter Name
Choose wich parameter is displayed on the home page at
Startup Display
power-up
Option
Value
Current
0
Voltage
1
Power
2
DEFAULT: Voltage
1
Neut-Eng-REVO-C-3PH-300-800A-Thyristors-Units
REVO C
Description
Value
0
15
10
11
12
12
Description
Resulting Signal
Resulting Signal
(4 to 20 mADC)
(0 to 20 mADC)
4mADC = 0%
0mADC = 0%
20mADC = 100%
20mADC = 100%
4mADC = 0V
0mADC = 0V
20mADC = xV
20mADC = xV
4mADC = 0A
0mADC = 0A
20mADC = xA
20mADC = xA
4mADC = 0%
0mADC = 0%
20mADC = 100%
20mADC = 100%
Description
Description
Default
0
Resulting Signal (0
to 10 VDC)
0VDC = 0%
10VDC = 100%
0VDC = 0V
10VDC = xV
0VDC = 0A
10VDC = xA
0VDC = 0%
10VDC = 100%
41
User's Manual
Modbus
Default
Address
12
68
Modbus
Range
Unit
Address
0 to 9999
124
Modbus
Default
Address
1
69
Modbus
Default
Address
1
60
Par.
Type
Read
Write
Par.
Type
Read
Write
Par.
Type
Read
Write
Par.
Type
Read
Write