Chapter 4. Serial Communications
4.1.4 Fast Key Sequence
Note: Use password 16363.
Sequence
Description
1,1,1
Snsr
1,1,2
AI % Rnge
1,1,3
AO1
1,2,1
Test Device
1,2,2,1
4 mA
1,2,2,2
20 mA
1,2,2,3
Other
1,2,2,4
End
1,2,3,1,1
4 mA
1,2,3,1,2
20 mA
1,2,3,1,3
Exit
1,2,3,2,1
PV LRV
1,2,3,2,2
PV URV
1,2,3,2,3
PV USL
1,2,3,2,4
PV LSL
1,2,4
D/A Trim
1,3,1
Tag
1,3,2
PV unit
1,3,3,1
PV LRV
1,3,3,2
PV URV
1,3,3,3
PV LSL
1,3,3,4
PV USL
1,3,4,1
Distributor
1,3,4,2
Model
1,3,4,3
Dev id
1,3,4,4
Tag
1,3,4,5
Date
1,3,4,6
Write Protect
1,3,4,7
Descriptor
1,3,4,8
Message
1,3,4,9
PV snsr s/n
1,3,4,menu
Final assy #
1,3,4,menu,1
Universal Rev
1,3,4,menu,2
Fld dev Rev
1,3,4,menu,3
Software Rev
1,3,5
PV Xfer fnctn
1,3,6
PV Damp
1,4,1,1
PV
82
Table 4: Fast Key Sequence
Access
View
Primary variable value
View
Analog output % range
View
Analog output, mA
N/A
Not used
View
Loop test, fix analog output at 4 mA
View
Loop test, fix analog output at 20 mA
Edit
Loop test, fix analog output at mA value entered
Exit loop test
N/A
Not used, apply values
N/A
Not used, apply values
Exit apply values
Edit
Primary variable lower range value
Edit
Primary variable upper range value
View
Primary variable upper sensor limit
View
Primary variable lower sensor limit
Edit
Calibrate electronics 4mA and 20mA values
Edit
Tag
Edit
Primary variable units
Edit
Primary variable lower range value
Edit
Primary variable upper range value
View
Primary variable upper sensor limit
View
Primary variable lower sensor limit
N/A
Not used
N/A
Not used
View
Device identification
Edit
Tag
Edit
Date
View
Write protect
Edit
Vortex flowmeter
Edit
32 character alphanumeric message
View
Primary variable sensor serial number
Edit
Final assembly number
View
Universal revision
View
Field device revision
view
Software revision
View
Linear
Edit
Primary variable damping (time constant) in seconds
View
Primary variable value
Notes