Energy-Saving Unit → PLC
Table 12 Remote I/O Table (Energy-Saving Unit → PLC)
Device
RX0
During Run/During Stop
RX1
During Regeneration
RX2
Terminals M1-M2 Function Multi-function output: H2-01
During Run (Converter
RX3
Ready)
RX4
Reserved
RX5
Undervoltage (Uv)
Terminals P1-PC
RX6
Function
Terminals P2-PC
RX7
Function
Momentary Power Loss
RX8
Ride-Thru/Recovery from
Momentary Power Loss
RX9
ComCtrlstatus/NetCtrlstatus
RXA
CC-Link Option Fault
RXB
During Active Current Limit
RXC
Obtain Monitor Data
RXD
Alarm
RXE
Fault
Command Code Execute
RXF
Complete
RX10
During Reset Signal Input
RX11
oPE Error
Power Supply Undervoltage
RX12
(AUv)
RX13
Reserved
to 19
RX1A
Error
YASKAWA ELECTRIC TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
Name
ON: During Run, OFF: During
Stop
ON: During Regeneration
Multi-function output: H2-02
<1>
Multi-function output: H2-03
<1>
Communication error between
energy-saving unit and CC-Link
device
ON: Monitor data has been
updated.
ON: Displayed after the specified
command code has been executed.
RXF signal switches off when the
RYF command is no longer
present.
ON: Fault occurred on the
energy-saving unit side.
Description
8 CC-Link Data Table
Default
H2-01 = 25: During
Run 1
H2-02 = 26: During MC ON
H2-03 = 6: Energy-Saving Unit
Ready
43