Device
Signal Name
RXD
Frequency Setting Ready 1
RXE
Frequency Setting Ready 2
Command Code Execute
RXF
Complete
RX10
Reserved
to 19
RX1A
Error
RX1B
Remote Station Ready
RX1C
Reserved
to 1F
<1> Terminals will differ depending on the model of the drive. Refer to
Model of the Drive on page 46
Note: If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the
register. Using RYE (Frequency Reference 2 flag) too often can shorten the performance life of
the drive's internal memory.
Energy-Saving Unit Remote I/O
n
PLC → Energy-Saving Unit
Table 11 Remote I/O Table (PLC → Energy-Saving Unit)
Device
Run Command/Automatic
RY0
Run Command
RY1
Forced Run Command
RY2
Terminal S3 Function
RY3
Terminal S4 Function
RY4
Terminal S5 Function
RY5
Terminal S6 Function
RY6
Terminal S7 Function
RY7
Terminal S8 Function
RY8
Reserved
YASKAWA ELECTRIC TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
ON: Displays the main frequency
reference that has been set.
ON: Displays the data set to d1-01
(Frequency Reference 1).
Also sets the main frequency
reference at the same time.
ON: Displayed after the specified
command code has been executed.
RXF signal switches off when the
RYF command is no longer
present.
ON: Fault occurred on the drive
side.
ON: Drive is ready to operate.
for information on terminals.
Name
ON: Run Command/Automatic
Run Command,
OFF: Stop Command
ON: Forced Run Command,
OFF: Stop
Multi-Function Input: H1-03
Multi-Function Input: H1-04
Multi-Function Input: H1-05
Multi-Function Input: H1-06
Multi-Function Input: H1-07
Multi-Function Input: H1-08
Description
–
–
Terminals that Change depending on the
Description
–
8 CC-Link Data Table
Default
–
–
–
–
–
–
–
Default
–
–
H1-03 = 24: External Fault
H1-04 = 14: Fault Reset
H1-05 = F: Through Mode
H1-06 = F: Through Mode
H1-07 = F: Through Mode
H1-08 = 8: Baseblock command
(N.O.)
–
41