8 CC-Link Data Table
Drive → PLC
Device
Signal Name
RX0
Forward Run
RX1
Reverse Run
YASKAWA AC Drive
1000-Series: Terminals M1,
M2 Function
RX2
YASKAWA AC Drive
GA700, GA800:
Multi-function digital output
1
RX3
Speed Agree
RX4
During Stall Prevention
RX5
During Undervoltage
YASKAWA AC Drive
1000-Series: Terminal P1
Function
RX6
YASKAWA AC Drive
GA700, GA800:
Multi-function digital output
2
<1>
YASKAWA AC Drive
1000-Series: Terminal P2
Function
RX7
YASKAWA AC Drive
GA700, GA800:
Multi-function digital output
3
<1>
RX8, 9
Reserved
RXA
CC-Link Option Fault
Monitoring Motor
RXB
Revolutions
RXC
Obtain Monitor Data
40
Table 10 Remote I/O Table (Drive → PLC)
ON: Forward Run Command
Present (includes DC Injection
Braking)
OFF: No Forward Run Command
ON: Reverse Run Command
Present
OFF: No Reverse Run Command
(includes DC Injection Braking)
Multi-function output: H2-01
ON: Output frequency is between
frequency reference and the
detection width set to L4-02.
<1>
Multi-function output: H2-02
<1>
Multi-function output: H2-03
Communication error between
drive and CC-Link device
ON: Currently monitoring motor
revolutions.
ON: Monitor data has been
updated.
YASKAWA ELECTRIC TOBP C730600 83C YASKAWA AC Drive Option SI-C3 Installation Manual
Description
Default
H2-01 = 0: During Run
H2-02 = 1: Zero Speed
H2-03 = 2: Speed Agree 1
Data is stored in remote register
RW
.
R1