Installation Guide Linear Motors
5.4
Attaching the cable shielding
Power Cable
Shrink tubing
Copper shielding
L-Connector (6 pin)
The power cable is supplied with a copper shielding (see illustration above). This prevents electrical and / or
magnetic fields. The shielded part of the cable must be grounded via a connection to the back wall of the
switchboard. The shielding has to be mounted holohedral to the connection part (see scheme above). The
shield connection terminal block is offered as an accessory for power cables and must be ordered separately
(Item-No. 0150-3631) However, the kind of attaching the cable shielding generally depends on the system of
the switchboard manufacturer.
5.5 Rotatability of motor connectors
The power connector and signal connector can be rotated in both directions. (see illustration below).
Power Connector
Page 18 / 41
Power Cable
Conductive
mounting plate
P10-70 / P10-70-D01/02/03
Signal Connector
NTI AG / LinMot
ENG
Shield connect.
terminal block
Servo Drive