Connection Of The Motor; Wiring Of The Motor; Terminal Block X1A Motor Connection; Figure 20: Wiring Of The Motor - KEB COMBIVERT F6 Instructions For Use Manual

Hide thumbs Also See for COMBIVERT F6:
Table of Contents

Advertisement

cONNecTION OF THe POWer UNIT

4.2.5 connection of the motor

4.2.5.1 Wiring of the motor

TA1 TA2
L1
U
L2
V
L3
W
PE
PE
Figure 20:
Wiring of the motor

4.2.5.2 Terminal block X1A motor connection

X1A
Figure 21:
Terminal block X1A motor connection
54
Legend
1
KEB COMBIVERT
Apply motor cable, shielding on both sides over a
2
large surface on the bare metallic frame or mount-
ing plate (remove paint if necessary)
U
3
Three-phase motor
V
W
PE
Temperature monitoring (optional)
4
=>
Name
Function
U, V, W
Motor connection
Instruction manual „Control circuit"
cross-section for
terminal connection
Flexible line with
wire-end ferrule
1.5...35 mm²
(without wire-end
ferrule up to max.
50 mm²)
UL: flexible line with-
out wire-end ferrule
AWG 16...1
Tightening
torque
3.2...3.7 Nm
28...32 lb inch