cerTIFIcATION

6.2 UL certifications

Acceptance according to UL is marked at KEB drive converters with the adjacent logo on
the nameplate.
To be conform according to UL for use on the North American and Canadian Market the
following additionally instructions must be observed (original text of the UL-File):
• All models: Maximum Surrounding Air Temperature: 45 °C
• Use 75°C Copper Conductors Only
• Models 19F6 and 20F6: Suitable For Use On A Circuit Capable Of Delivering Not
• Integral solid state short circuit protection does not provide branch circuit protec-
• For installations according to Canadian National Standard C22.2 No. 274-13:
• Control Circuit Overcurrent Protection Required or equivalent.
• WARNING – The opening of the branch circuit protective device may be an
• Internal Overload Protection Operates prior to reaching the 130% of the Motor Full
This marking is only applicable for all power field wiring terminals.
More Than 5000 rms Symmetrical Amperes, 480 Volts Maximum when protected
by Class J Fuses, see instruction manual for Branch Circuit Protection details.
Models 21F6 and 22F6: Suitable For Use On A Circuit Capable Of Delivering Not
More Than 10000 rms Symmetrical Amperes, 480 Volts Maximum when protected
by Class J Fuses, see instruction manual for Branch Circuit Protection details.
All models: Suitable For Use On A Circuit Capable Of Delivering Not More Than
30000 rms Symmetrical Amperes, 480 Volts Maximum when protected by Sem-
iconductor Fuses by SIBA, Type 20 189 20, or by EATON, Type 170M1368, see
instruction manual for Branch Circuit Protection details.
CSA: For Canada, this marking shall be provided on the device or on a separate
label shipped with the device.
Details of the prescribed Branch Circuit Protection as specified in the below sec-
tion 'Branch Circuit Protection' of this Report need to be marked in the instruction
manual.
tion. Branch circuit protection must be provided in accordance with the Manufac-
turer Instructions, National Electrical Code and any additional local codes.
CSA: For Canada: Integral solid state short circuit protection does not provide
branch circuit protection. Branch circuit protection must be provided in accordance
with the Canadian Electrical Code, Part I"
For use in Pollution Degree 2 and Overvoltage Category III environments only.
indication that a fault current has been interrupted. To reduce the risk of fire or
electrical shock, current-carrying parts and other components of the controller
should be examined and replaced if damaged. If burnout of the current element of
an overload relay occurs, the complete overload relay must be replaced.
Load Current, see manual for adjustment instructions or equivalent wording.
69