cONNecTION OF THe POWer UNIT
4.2.4 Dc connection
4.2.4.1 Connection at DC voltage supply
Legend
1
DC voltage
2
Fuses
3
KEB COMBIVERT
Figure 18:
Connection at DC voltage supply
4.2.4.2 Terminal block X1A DC connection
X1A
Figure 19:
Terminal block X1A DC connection
+U
-U
PE
Pay attention to the permissible voltage range !
The use of DC terminals for feed-in is permitted only permitted with external
precharging.
Name
Function
DC connection,
connection for
+, -
interconnected opera-
+
U
V
-
W
PE
PE
400 / 480 V class: U
dc
Type aR
max. occurring DC voltage of 840 V
F6
cross-section for
terminal connection
Flexible line with
wire-end ferrule
1.5...35 mm²
(without wire-end
ferrule up to max.
50 mm²)
tion
UL: flexible line with-
out wire-end ferrule
AWG 16...1
= 390...780 V
Tightening
torque
3.2...3.7 Nm
28...32 lb inch
53