cONNecTION OF THe POWer UNIT

4.2.3 Ac connection

4.2.3.1 AC supply 400 V / 3-phase

L1
L2
L3
PE
No.
Typ
Mains voltage
Mains form
Personal protection
Mains fuses
Mains contactor
Mains choke
HF filter for TN-, TT
systems
HF filter for IT systems
KEB COMBIVERT
Figure 17:
Connection of the mains supply 400 V / 3-phase

4.2.3.2 Supply line

The conductor cross-section of the supply line is determined by the following factors:
PE
The rated voltage between one phase conductor and earth potential (or arti-
ficial neutral point in the IT mains) must not exceed 300 V (effective value).
RCMA with separator or RCD type B
Required for compliance with the limit values in accordance with
input current of the drive converter
used cable type /
installation and ambient temperatures
applicable local electrical regulations
The application engineer is responsible for the design.
L1
L2
L3
PE
PE
Description
3-phase 400 V
TN, TT
Type gG or MCCB
see notes under the table
F6
U
V
W
PE
IT
Insulation monitors
EN 61800-3.
51