SPECIFICATIONS

4.
Specifications
Supply
Mains Voltage (U
)
r
MVE-xxxx-V02
MVE-xxxx-V03
MVE-xxxx-V04
MVE-xxxx-V06
MVE-xxxx-V11
MVE-xxxx-V13
Rated Frequency (fr) .............................................................................................................................................................. 50/60 Hz
Rated lightning impulse withstand voltage (U
MVE-xxxx-V02 ~ V06 ............................................................................................................................................................ 60 kV
MVE-xxxx-V11
MVE-xxxx-V13
Rated power frequency withstand voltage (U
MVE-xxxx-V02 ~ V06 ............................................................................................................................................................ 20 kV
MVE-xxxx-V11 ~ V13 ......................................................................................................................................................
Rated normal current (l
MVE-0070-Vxx .......................................................................................................................................................................
MVE-0110-Vxx .....................................................................................................................................................................
MVE-0200-Vxx .....................................................................................................................................................................
MVE-0220-Vxx .....................................................................................................................................................................
MVE-0250-Vxx .....................................................................................................................................................................
MVE-0300-Vxx .....................................................................................................................................................................
MVE-0360-Vxx .....................................................................................................................................................................
MVE-0400-Vxx .....................................................................................................................................................................
MVE-0450-Vxx .....................................................................................................................................................................
MVE-0500-Vxx .....................................................................................................................................................................
MVE-0540-Vxx .....................................................................................................................................................................
MVE-0600-Vxx .....................................................................................................................................................................
MVE-0700-Vxx .....................................................................................................................................................................
MVE-0800-Vxx .....................................................................................................................................................................
MVE-0900-Vxx .....................................................................................................................................................................
MVE-1000-Vxx ................................................................................................................................................................... 1000 A
MVE-1100-Vxx ................................................................................................................................................................... 1100 A
MVE-1200-Vxx ................................................................................................................................................................... 1200 A
MVE-1300-Vxx ................................................................................................................................................................... 1300 A
MVE-1400-Vxx ................................................................................................................................................................... 1400 A
MVE-1500-Vxx ................................................................................................................................................................... 1500 A
MVE-1600-Vxx ................................................................................................................................................................... 1600 A
MVE-1700-Vxx ................................................................................................................................................................... 1700 A
Rated short-time withstand current (symmetrical RMS) (l
MVE-xxxx-V02 ~ V06 ...........................................................................................................................................................
MVE-xxxx-V11 ~ V13 ...........................................................................................................................................................
Form designation ................................................................................................ Bypassed semiconductor motor starter form 1
Control voltage
................................................................................................................................
Rated Frequency .................................................................................................................................................................... 50/60 Hz
Typical power consumption
8
| MVE User Manual (710-17074-00G)
............................................................................................................................................ 2.3 kV Phase-phase
............................................................................................................................................ 3.3 kV Phase-phase
.......................................................................................................................................... 4.16 kV Phase-phase
............................................................................................................................................ 6.6 kV Phase-phase
.......................................................................................................................................... 11.0 kV Phase-phase
.......................................................................................................................................... 13.8 kV Phase-phase
)
1
p
...................................................................................................................................................................... 75 kV
...................................................................................................................................................................... 95 kV
)
1
d
)
r
................................................................................................................................. 70 W continuous
)
2
k
~ 42 kV
70 A
110 A
200 A
220 A
250 A
300 A
360 A
400 A
450 A
500 A
540 A
600 A
700 A
800 A
900 A
48 kA
50 kA
85 ~ 264 VAC or 90 ~ 350 VDC
3
4

Hide quick links: