CONTROLLER
CAUTION
Continued use of Emergency Run is not recommended. Emergency Run may compromise the starter life as all
protections and trips are disabled.
Using the starter in 'Emergency Run' mode will void the product warranty.
16 Protection Action
These parameters define how the soft starter will respond to different protection events. The soft starter can trip, issue a warning,
or ignore different protection events as required. All protection events are written to the event log. The default action for all
protections is to trip the soft starter.
CAUTION
Defeating the protection may compromise the starter and motor, and should only be done in the case of emergency.
16A~16W – Protection Actions
Options:
Trip Starter (default)
Warn and Log
Log Only
Description:
Selects the soft starter's response to each protection.
•
16A
•
16B
16C
•
•
16D
•
16E
16F
•
•
16G
•
16H
16I
•
•
16J
•
16K
16L
•
•
16M
•
16N
16O~16U
•
•
16V
•
16W
20 Restricted
These parameters are restricted for Factory use and are not available to the user.
60
| MVE User Manual (710-17074-00G)
Motor Overload
Excess Start Time
Undercurrent
Instantaneous Overcurrent
Current Imbalance
Frequency
Input A Trip
Input B Trip
Motor Thermistor
Starter Communication
Network Communication
Reserved
Battery/Clock
Ground Fault
Reserved
Undervoltage
Overvoltage