Using points
Information about the point, including its ID, appears in the Message Zone.
2. Click
The point's parameters turn gray to indicate that the point is disabled.
To enable a disabled point
1. Select an editable display object associated with the point—for example, an alpha-
numeric that shows the PV. (The object is editable if the value appears in 'inverse
video' when you select it.)
Information about the point, including its ID, appears in the Message Zone.
2. Click
To disable an EFM meter
1. Display the meter in the meter detail display.
2. Clear the Enable check box.
When you disable a meter, any of its currently executing schedules are abandoned.
To enable a disabled EFM meter
1. Display the meter in the meter detail display.
2. Select the Enable check box.
When you enable a disabled meter:
Data collection will begin at either the next scheduled interval or when a manual
l
collection is requested.
Because of the potentially large load this may have on channels and controllers,
l
there will be some throttling of EFM traffic. If a request for EFM data is delayed
due to throttling, this will not be considered a failed request. Accordingly, this
does not affect the retry count.

Adding a red tag or operator tag to a point

This topic is applicable to only certain points.
When maintaining equipment, you may need to temporarily bring a point out of service (add a
red tag), or add a maintenance comment (operator tag) to a point: