Viewing Historical Information About Alarm Suppression - Honeywell Experion LX Operator's Manual

Hide thumbs Also See for Experion LX:
Table of Contents

Advertisement

Responding to alarms
Whether the setting was changed from Disabled to Enabled.
l
Whether the suppression group whose setting you changed is currently active or not.
l
An event records the "override" and the following information:
n
The operator name (or Station number).
l
The name of the group to which the override has been applied.
l
The new enabled/disabled setting of the group.
l

Viewing historical information about alarm suppression

Whenever an alarm is suppressed or unsuppressed, the Experion event system records
information about the alarm or suppression group. For example, the event system records:
The name of the suppression group the alarm belongs to.
n
When the suppression group started (or stopped) suppressing alarms.
n
Which alarms activated (or deactivated) the suppression group.
n
Which alarms have been suppressed by the suppression group.
n
Whether a group has been enabled or disabled, and if so, by whom and when.
n
When a group was last loaded and by whom.
n
This historical information is useful for post-incident analysis or troubleshooting, especially
for alarms in suppression groups that are no longer active and therefore no longer available in
the (suppressed alarms) view of the Alarm Summary.
As with any other type of alarm-related event, you can access historical information about
alarm suppression via the Event Summary display.
You can also run an Alarm and Event Report to view event information for specific points or
assets that were involved in the alarm suppression events that you want to investigate.
Viewing alarm suppression information via the Event Summary
1. On Station, call up the Event Summary.
2. Use the column filter options for Suppression Group or Flags to locate event details
related to alarm suppression.
Because the default view of the Event Summary does not include these columns, you
may need to use the Column Organizer to add them.