Alarm Summary Columns - Honeywell Experion LX Operator's Manual

Hide thumbs Also See for Experion LX:
Table of Contents

Advertisement

Responding to alarms

Alarm Summary columns

The following table describes the default alarm line items, starting from the left.
Tip:
The alarm colors described below are the default alarm colors. Your system
n
may use custom alarm colors.
When an alarm is disabled, the original icon shape is retained, but the
n
symbol changes to a minus sign and its color changes to gray.
Column
Alarm
state
Honeywell 2017
Active State
Meaning
Magenta and flashing:
the alarm is critical
priority,
unacknowledged and
the cause of the alarm
still exists.
Magenta and not
flashing: the alarm is
critical priority,
acknowledged and the
cause of the alarm still
exists.
Inverse color and
flashing: the alarm is
critical priority,
unacknowledged and
the cause that
generated the alarm no
longer exists.
Red and flashing: the
alarm is urgent
priority,
unacknowledged and
the cause of the alarm
still exists.
Red and not flashing:
the alarm is urgent
Bad quality
Disabled state
state
106