Fuji Electric NA0AX06-MR User Manual page 49

Micrex-sx spf series analog unit
Table of Contents

Advertisement

Section 3 Programming
(2) Thermocouple input unit (Target type: NA0AX02-TC, NA0AX06-TC, NA0AX16-TC)
For a thermocouple input unit, set the sensor type of the thermocouple, moving average execution times, sampling period, and
unit.
Parameter
Sensor type
Moving average
Sampling period
Unit
<How to set parameters>
1) Right-click the thermocouple input unit registered in the system definition screen and left-click [Properties]. The "Module
properties" dialog box opens.
2) Click the [Parameter] button to display the "Temperature Measurement Unit parameter setting" dialog box.
Set the sensor type, moving average, sampling period, and unit for all channels in a batch, and then click the [OK] button.
Setting range
J: -200 to 1200°C
K: -200 to 1200°C
T: -190 to 380°C
E: -190 to 1000°C
N: -200 to 1000°C
B: 350 to 1800°C
R: 0 to 1800°C
S: 0 to 1700°C
No moving average, 2, 4, or 8 times
High speed or low speed
Celsius or Fahrenheit
3-7