Fuji Electric NA0AX06-MR User Manual page 14

Micrex-sx spf series analog unit
Table of Contents

Advertisement

Section 2 Specifications
(4) Analog output board, 2 channels NA3AY02-MR
Item
Type
No. of output channels
External load resistance
Analog output range
Resolution
Overall accuracy
Data type of digital output value INT type
Output period
External wire connections
Applicable wire size
Status indication
Isolation method
Occupied words
Internal current consumption
Mass
*1 Tightening torque for mounting the board on the main unit: 0.2 N·m
*2 Notes on using analog output
The analog unit does not support the hold function. If the main unit stops due to a system error, the analog output value
becomes 0 (zero). It is not possible to hold the output status after occurrence of an error or CPU stop.
Specification
NA3AY02-MR
2 channels
Voltage output: 1k W to 1MW, Current output: 0 to 500 W or less
0 to +10V
0 to 20mA
* Selectable by wiring of the terminal block.
12 bits
±1%
Synchronized with the scan of the main unit.
5-pole European-style terminal block (M2) x 1, Tightening torque: 0.2 N·m
AWG#28-16 * Be sure to use shielded twisted pair cables.
None
Not isolated
2 words
5V DC, 223mA
Approx. 20g
2-5

Hide quick links: