Section 2 Specifications
(2) Functions
1) Status indication LED
Status indication LED
PWR of analog input unit
2) Terminal block
These are terminals for 24V DC power supply to operate the analog unit and analog input signal.
NA0AX06-MR
3) JP1: Digital value range selection
This jumper pin is used to set the digital value range.
Digital value range
-8192 to 8191
0 to 16383
4) JP2 and JP3: Analog input range selection
These jumper pins are used to set the analog signal range
for six channels in a batch.
Signal range
JP3 setting
0 to 10V
B
or
0 to 20mA
U
0 to 5V
B
or
0 to 10mA
U
-10 to 10V
B
or
-20 to 20mA
U
-5 to 5V
B
or
-10 to 10mA
U
* When handling the setting pins on the printed circuit board, be sure to turn OFF the unit power. Securely mount them by using
tweezers.
Status
Specification
ON (red)
While 5V DC power is normally supplied.
* For the wiring method, see "2-4 Wiring."
JP1 setting
JP2 setting
5V
10V
5V
10V
5V
10V
5V
10V
5) JP4 to 9: Voltage/current selection
This jumper pin is used to select voltage or current for
each channel.
Voltage/current
Voltage
Current
2-16
Setting of
JP4 (CH0) to JP9 (CH5)
V
I
V
I