Section 2 Specifications; General Specifications - Fuji Electric NA0AX06-MR User Manual

Micrex-sx spf series analog unit
Table of Contents

Advertisement

Section 2 Specifications

2-1 General Specifications

Item
Physical
Operating ambient
temperature
environmental
conditions
Storage (transportation)
temperature
Relative humidity
Pollution degree
Corrosion immunity
Operating altitude
Mechanical
Vibration
service
conditions
Shock
Electrical
Electrostatic discharge
service
Radiated,
conditions
radio-frequency,
electromagnetic field
EFT/B (Electrical fast
transient/burst)
Lightning impulse surge AC equipment power: ±2kV common mode, ±1kV differential mode
Conducted radio
frequency
Power frequency
magnetic field
Construction
Cooling
Notes:
1) Pollution degree 2: This pollution does not conduct usually, but under certain circumstances temporary conductivity occurs
due to condensation.
2) The unit is fixed by screws to the control panel. When the unit is mounted to the DIN rail, care must be taken that
vibrations or shocks will not occur.
3) In an environment where repetitive or continuous vibration occurs, be sure to take vibration-proofing measures.
Specification
0 to +55°C
-25 to +70°C
20 to 95%RH, no condensation
(Transport condition: 5 to 95%RH, no condensation)
2 (Note 1)
Free from corrosive gases. Not stained with organic solvents
2000 m or less above sea level (Transport condition: 70 kPa or more)
Half amplitude: 0.15mm, Constant acceleration: 19.6 m/s
Two hours for each of three mutually perpendicular axes, total six
hours.
Acceleration peak: 98 m/s
Three times for each of three mutually perpendicular axes.
Contact discharge: ±4kV, Aerial discharge: ±8kV
80 to 1000MHz (10V/m)
1.4 to 2.0 GHz (3V/m)
2.0 to 2.7 GHz (1V/m)
Equipment power, I/0 power, AC I/O (unshielded): ±2kV
Data communication, digital and analog I/O s' (except AC unshielded
I/O): ±1kV
DC equipment power: ±0.5kV common mode, ±0.5kV differential mode
150kHz to 80MHz, 10V
50Hz, 30A/m
Panel-mounted type (open equipment)
Air cooling
2-1
2
Remark
IEC 61131-2
2
(Note 2) (Note 3)
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents