Fuji Electric NA0AX06-MR User Manual page 12

Micrex-sx spf series analog unit
Table of Contents

Advertisement

Section 2 Specifications
(2) Analog output unit NA0AY02-MR
Item
Type
No. of output channels
External load resistance
Analog output range
Resolution
Overall accuracy
Data type of digital output value INT type
Output period
External wire connections
Applicable wire size
Status indication
Isolation method
Occupied words
External power supply
Internal current consumption
Dimensions
Mass
*1 Notes on using analog output
The analog unit does not support the hold function. If the main unit stops due to a system error, the analog output value
becomes 0 (zero). It is not possible to hold the output status after occurrence of an error or CPU stop.
Specification
NA0AY02-MR
2 channels
Voltage output: 500 W to 1 MW, Current output: 0 to 500 W or less
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
14 bits
±1%
Synchronized with the scan of the main unit.
8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
AWG#22-18 * Be sure to use shielded twisted pair cables.
5V power supply display, ON when normal (red)
Not isolated * For the internal circuit, see "Appendix 2."
2 words
24V DC, 90mA *Wiring length: 10m or less
5V DC, 33mA
40 (W) x 90 (H) x 80 (D) (mm)
Approx. 140g
2-3