Fuji Electric NA0AX06-MR User Manual page 30

Micrex-sx spf series analog unit
Table of Contents

Advertisement

Section 2 Specifications
6) JP3 and JP4: Analog input range selection
Signal range
JP3 setting
0 to 10V
U
or
0 to 20mA
B
0 to 5V
U
or
0 to 10mA
B
-10 to 10V
U
or
-20 to 20mA
B
-5 to 5V
U
or
-10 to 10mA
B
7) JP5 to 8: Input voltage/current selection
This jumper pin is used to select voltage or current for each channel.
Setting of
Voltage/current
JP5 (CH0) to JP8 (CH3)
Voltage
Current
* When handling the setting pins on the printed circuit board, be sure to turn OFF the unit power. Securely mount them by using
tweezers.
JP4 setting
5V
10V
5V
10V
5V
10V
5V
10V
2-21