Other Functions; Mode Setting - Fuji Electric Micro Control X Instruction Manual

Table of Contents

Advertisement

Creating a ramp soak operation pattern
Set the following items to create a pattern.
Sets which steps to use from the following 15 types.
Pattern
Target SV
Sets the controlled temperature.
Ramp time
Sets the time to reach the target SV from the current SV.
Soak time
1
") and choose pattern 0 (" ").
2
3
Sets the units of time. Besides minute:second ("
("
")
4
") and set the target temperature.
5
6
7
Running ramp soak
1
2
Ramp soak starts running from the current PV.
Point
" will display when ramp soak has completed.
SV is counted towards soak time.
process value
guaranty soak
range upper limit
guaranty soak
range lower limit
and a lower limit of 3°C.
1
2
3
4
5
Press the
key to set the value.

Mode setting

Sets how you want to run ramp soak.
The following items can be set.
Power On Start
Ramp Soak starts running from the current PV.
Ending Output
Shows the ending output after ramp soak has been completed.
OFF Output
Shows the output during OFF after ramp soak has been completed.
Repeat Behavior
repeats
2nd soak
2nd ramp
SV-2
1st ramp
1st soak
power on
start
SV-1
PV
TM1r
TM1S
TM2r
TM2S
TM3r
").
") and choose minute:second ("
").
"), you can also choose hour:minute
") and set the ramp time.
") and set the soak time.
").
") in step 2. To cancel the
") again.
soak time=T1+T2+T3
T1
T2
T3
PV
SV
t
").
") and choose on ("
").
") and set the lower limit (in this
") and set the upper limit (in this
4th soak
SV-4
4th ramp
3rd ramp
3rd soak
SV-3
following 16 types of modes
according to the combination
of run method options.
TM3S
TM4r
TM4S
Setting
Power On Start
Ending Output
"0"
Off
Continuous control
"1"
Off
Continuous control
"2"
Off
Continuous control
"3"
Off
Continuous control
Off
Standby
"5"
Off
Standby
"6"
Off
Standby
Off
Standby
On
Continuous control
"9"
On
Continuous control
"10"
On
Continuous control
"11"
On
Continuous control
"12"
On
Standby
"13"
On
Standby
On
Standby
"15"
On
Standby
PV start
(PV) and the program pattern match, and starts operation at that point.
PV=(1)
PV=(2)
SV
PV=(3)
Start of
(3)

7-10. Other Functions

1. Soft start function
When turning on the equipment (including the temperature controller), the soft start function
amount of time after power is turned on.
This function is useful for effects such as suppressing the heater output during equipment startup, and
makes load lightened.
function ends and normal controls begin.
Parameter
MV1 soft start output set value
"
" (SFo1)
Soft start set time
"
" (SFTM)
soft start output
set value
The soft start function cannot be used simultaneously with the dual control
Caution
(Be sure to set 0.00 during dual control.)
Point
keep track of the set time period.
Use the following steps to set soft start output set value and set time.
1
2
3
Press the
key to set the value.
4
Turn off the power once, and then re-start the controller to begin soft start. (When the soft start
5
function is turned on, the lower display will alternate showing SoFT and SV.)
- 16 -
OFF Output
Continuous control
Continuous control
Standby
Standby
Continuous control
Continuous control
Standby
Standby
Continuous control
Continuous control
Standby
Standby
Continuous control
Continuous control
Standby
Standby
Start of
(2)
Start of
Function
Places a limit on MV1 output after power is turned on for a time
period set in SFTM.
Sets the time for soft start to function after turning power on.
Setting "0" will turn off soft start.
control output (MV)
MV when not using
soft start
MV when using
soft start (limited)
0%
t
soft start
power on
set time
").
").
") and set the time.
Repeat Behavior
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
(1)