Acs Program Mapping - Notifier ACS Series Installation Manual

Annunciator control system
Hide thumbs Also See for ACS Series:
Table of Contents

Advertisement

AM2020/AFP1010 Systems
P.7 ACS Program Mapping
ACS points "track" or follow those system points they are programmed to
annunciate; the annunciator points do not latch. Table P-1, which follows, lists
how the ACS annunciates various devices and functions.
Point Type
Control Module
XPC Circuit
XPR Circuit
XPIQ Speaker and
Telephone/Strobe Circuits
Monitor Module
XPM Circuit
XPIQ Monitoring
XP5-M
Intelligent Detector
Software Zone
1
ACK/STEP
1
SIGNAL SILENCE
2
SYSTEM RESET
2
LAMP TEST
Table P-1 Annunciator Program Mapping with AM2020/AFP1010
Note: Control Switches marked "not used" will still function as local LAMP TEST
switches for their respective LEDs.
66
ACM-48A or
ACM-32A Module &
AEM-48A or
AEM-32A Expander
Active LED
Indicates on/off status
of module or circuit
Indicates alarm status
of module or circuit
Indicates alarm status
of detector
Indicates active status
of software zone
Indicates System
Alarm
Not used
Indicates System
Alarm
Not used
1. In older systems, if the monitor module or XPM-8 circuit is programmed as a
supervisory point (SPSU), illumination of the trouble LED will occur for both
trouble and supervisory conditions. The exact status of the point (trouble versus
supervisory condition) can be read at the AM2020/AFP1010 control panel.
Prior to software release M2.8, supervisory points do not activate the point active
LEDs of an annunciator.
2. With the AM2020/AFP1010, the functions of ACK/STEP, SIGNAL SILENCE,
SYSTEM RESET and LAMP TEST may be assigned (mapped) to multiple
annunciator points.
ACM-24AT or ACM-16AT Module and
AEM-24AT or AEM-16AT Expanders
Trouble LED
Indicates trouble
status of module or
circuit
Indicates trouble
1
status of module or
1
circuit
Indicates trouble
status of detector
Indicates System
Trouble
Indicates System
Trouble
Indicates Signals
Silence
Indicates System
Trouble
Not used
Control Switch
Turns module on/off
Not used
Not used
Not used
ACK/STEP key
SIGNAL SILENCE
key
SYSTEM RESET key
LAMP TEST key