Cable Cross-Sections - Eaton PowerXL DB1 Installation Manual

Variable frequency drives
Hide thumbs Also See for PowerXL DB1:
Table of Contents

Advertisement

5.4 Cable cross-sections

Type of device
Frame
size
Voltage class 230 V
Mains voltage (50/60 Hz) U
LN
U
230 V AC, single-phase / U
e
DB1-122D3...
FS1
DB1-124D3...
FS1
Voltage class 400 V
Mains voltage (50/60 Hz) U
LN
U
400 V AC, three-phase/ U
e
DB1-342D2...
FS1
DB1-344D1NN...
FS1
1) AWG = American wire gauge
kcmil = Thousands of circular mils (1 kcmil = 0.5067 mm²)
The "Maximum terminal capacity" specification indicates the maximum pos-
sible sizes that can be connected to the power terminals. The cross-sectional
areas and gauges that should be used for the power supply and motor con-
nections are recommendations for the corresponding frame sizes and ratings
and are provided as examples.
Use the general installation instructions and local conditions as a
basis when selecting terminal capacities.
Table 12: Cable cross-sections
Maximum
Input current
terminal capacity
I
LN
2
mm
AWG/
A
1)
kcmil
200 (-10 %) – 240 (+10 %) V
230 V AC, three-phase
2
1.5
12
3.7
1.5
12
7.5
380 (-10 %) – 480 (+10 %) V
400 V AC, three-phase
2
1.5
12
3.5
1.5
12
5.6
DB1 Variable Frequency Drives 09/17 MN040031EN www.eaton.com
Assigned cross-
Output
sectional area for the
current (rated
power supply
current) I
(L1/L, L2/N, L3, PE)
2
mm
AWG/
A
1)
kcmil
1.5
14
2.3
1.5
14
4.3
1.5
14
2.2
1.5
14
4.1
5 Technical Data
5.4 Cable cross-sections
Assigned cross-
sectional area for the
motor connection
e
(U, V, W, PE)
2
mm
AWG/
kcmil
1.5
14
1.5
14
1.5
14
1.5
14
1)
81