3.3.2 Cooling measures

In order for variable frequency drive DB1 to operate reliably, sufficient cooling
is crucial. An essential aspect of efficient cooling is its thermal resistance,
including optimal thermal transfer between the cooling surface of the DB1
variable frequency drive and the cooling system (e.g. heatsink, mounting
plate, or machine housing). A heating plate is required for this purpose, and
the correct torque (2 Nm) must also be used for the fixing screws (3 x M4x20).
2
Figure 14: Cooling measures
The permitted temperature on the variable frequency drive cooling surface
depends on the switching frequency set with P-17. On delivery of the device,
this is 8 Hz.
Table 5: Temperature on the cooling surface
Switching
Permitted temperature T
frequency
the cooling surface of
variable frequency drive DB1
4 kHz
95 °C
8 kHz
90 °C
12 kHz
85 °C
16 kHz
80 °C
24 kHz
75 °C
32 kHz
70 °C
DB1 Variable Frequency Drives 09/17 MN040031EN www.eaton.com
3
2 Nm (17.7 lb-in")
3 x M4 x 20
1
on
CP
3 Installation
3.3 Assembly
43