Advertisement

Technical Data
Motor feeder
Output voltage
Assigned motor rating
at 230 V, 50 Hz
at 400 V, 50 Hz
Output frequency
Range, parametrizable
resolution
Rated operating current
Overload current for 60 s every 600 s
Overload current for 3.75 s every 600 s
Switching frequency (double modulation)
Operating mode
V/Hz control (speed accuracy)
Vector control (static speed accuracy)
Torque response time
Torque linearity
Response time (enable IGBT)
DC braking
Time before start
Motor pick-up control function (for catching spinning
motors)
DB1 Variable Frequency Drives 09/17 MN040031EN www.eaton.com
Symbol
Unit
Value
U
V
3~ 0 - U
2
P
kW
0.37 - 0.75
P
kW
0.75 - 1.5
f
Hz
0 - 5 x Motor Nom Frequency (P-09), max. 500 Hz
2
Hz
0.1
I
A
2.2 - 4.3
e
I
%
150
L
I
%
175
L
f
kHz
max. 32
PWM
±20 %, with slip compensation
±1 % load range: 0 % - 100 %
t
ms
1 - 8
r
±5 % (10 - 90 % of speed adjustment range,
20 - 100% of torque load range)
t
ms
<10
r
t
s
0 - 25, in the event of a stop
all frame sizes
5 Technical Data
5.1 General rated operational data
e
75