1.4.3 Features
1.4.4 DB1-12... device series
Part no.
DB1-122D3FN-N2CC
DB1-124D3FN-N2CC
1.4.5 DB1-34... device series
Part no.
DB1-342D3FN-N2CC
DB1-344D3FN-N2CC
The rated current I
mitted permanent current at optimum cooling conditions (→ section 3.3.2,
"Cooling measures", page 43).
Where cooling is reduced, this value may be lower. The reduction in this
value depends upon the application, and it cannot usually be specified in
advance.
Mains supply voltage:
Motor connection voltage: 3 AC (220 - 240) V
Table 2:
DB1-12... device series
Rated current
Assigned motor output
I
P
e
230 V, 50 Hz
A
kW
2.3
0.37
4.3
0.75
Mains supply voltage:
Motor connection voltage: 3 AC (380 - 480) V
Table 3:
DB1-34... device series
Rated current
Assigned
motor output
I
P
e
400 V, 50 Hz
A
kW
2.2
0.75
4.1
1.5
DB1 Variable Frequency Drives 09/17 MN040031EN www.eaton.com
indicated in Tables 2 and 3 below is the maximum per-
e
1 AC (220 - 240) V ( ±10 %)
P
(220 - 240) V, 60 Hz)
HP
1/2
1
3 AC (380 - 480) V ( ±10 %)
P
(440 - 480) V, 60 Hz
HP
1
2
Radio inter-
Frame size
ference
suppression
filter
✓
FS1
✓
FS1
Radio inter-
Frame size
ference
suppression
filter
✓
FS1
✓
FS1
1 DB1 series
1.4 Rated data
Brake
chopper
–
–
Brake
chopper
–
–
17