Eaton PowerXL DB1 Installation Manual page 61

Variable frequency drives
Hide thumbs Also See for PowerXL DB1:
Table of Contents

Advertisement

3.5.2.1 Terminal capacities and stripping lengths
Control signal terminals
Relay connection
n/a = not applicable
3.5.2.2 Control signal terminal connection information and functions
Table 8: Terminal capacities and stripping lengths
Strip length
mm
in
6 - 7
0,25
8 - 9
0,3
The functions that are set in the factory and the electrical connection data of
all control signal terminals are listed in the following table.
Table 9: Factory-set functions of the control terminals
Connection
Signal
terminal
1
+24 V
Control voltage for
DI1 – DI4, output
(+24 V)
2
DI1
Digital Input 1
3
DI2
Digital Input 2
4
DI3
Digital Input 3
AI2
Analogue Input 2
5
+10 V
Reference voltage,
Output (+10 V)
6
AI1
Analogue Input 1
DI4
Digital Input 4
7
0 V
Reference potential
8
AO1
Analogue output 1
DO1
Digital output 1
9
0 V
Reference potential
10
Modbus+
11
Modbus-
Relay output (RO1)
DB1 Variable Frequency Drives 09/17 MN040031EN www.eaton.com
Connection cross-
section, solid-core
mm
2
AWG
mm
max. 0,5
max. 20
max. 0,5
max. 1,5
max. 14
max. 1,5
Description
maximum load 100 mA,
Reference potential 0 V
Caution:
Do not connect an external voltage
source!
+8 - +30 V (High, R
+8 - +30 V (High, R
• Digital: +8 - +30 V (High)
• Analogue: 0 - +10 V (R
0/4 - 20 mA (R
switchable using parameter P-16
Maximum load: 10 mA
Reference potential: 0 V
• Digital: +8 - +30 V (High)
• Analogue: 0 - +10 V (R
0/4 - 20 mA (R
switchable using parameter P-16
0 V = connection terminal 9
• Digital: 0 - +24 V, maximum 20 mA
• Analog: 0 - +10 V, maximum 20 mA
switchable using parameter P-25
0 V = connection terminal 7
Potential-free N/O contact
250 V/6A AC1
30 V/5A DC1
3.5 Electrical Installation
Connection cross
Connection cross
section, fine-strand
section, fine-strand
2
AWG
mm
max. 20
n/a
max. 14
n/a
Default settings
> 6 kΩ)
Start enable FWD
i
> 6 kΩ)
Start enable REV
i
Fixed frequency FF1
> 72 kΩ)
i
= 500 Ω)
B
Frequency reference
> 72 kΩ)
(fixed frequency)
i
= 500 Ω)
B
Output frequency
RUN
3 Installation
with ferrule
2
AWG
n/a
n/a
57

Advertisement

Table of Contents
loading