2.8.6 Connecting EX motors
The following aspects must be taken into account when connecting explo-
sion-protected motors:
•
A DB1 variable frequency drive can be installed in an Ex-area or in a
control cabinet outside of the Ex area.
•
All applicable industry-specific and country-specific regulations for
explosion protection areas (ATEX 100a) must be complied with.
•
The specifications and instructions provided by the motor's manufac-
turer with regard to operation with a variable frequency drive – e.g.,
whether motor reactors (dV/dt limiting) are required – must be taken into
account.
•
Temperature monitors in the motor windings (thermistor, Thermo-Click)
must not be connected directly to the variable frequency drive, but
instead must be connected through a relay approved for the Ex area
(e.g. EMT6).
DB1 Variable Frequency Drives 09/17 MN040031EN www.eaton.com
2 Engineering
2.8 Three-phase motors
39