Eaton PowerXL DB1 Installation Manual page 64

Variable frequency drives
Hide thumbs Also See for PowerXL DB1:
Table of Contents

Advertisement

3 Installation
3.5 Electrical Installation
3.5.2.4 RJ45 interface
60
The RJ45 interface located on the front makes it possible to connect directly
to communication modules and fieldbuses.
The internal RS485 connection transmits Modbus RTU and CANopen data.
1
PIN 8
(PIN 2)
PIN 7
(PIN 1)
Figure 27: RJ45 interface
Table 10: Configuration of the RJ45 interface
Pin
Significance
1
CANopen -
2
CANopen +
3
0 V
4
OP-Bus -
5
OP-Bus +
6
+24 V
7
Modbus RTU (A), RS485-
8
Modbus RTU (B), RS485+
The way the RJ45 interface works is described in the following
manuals:
MN040018: "Modbus RTU – Communication manual for
DA1, DC1, DE1 variable frequency drives"
MN040019: "CANopen – Communication manual for DA1,
DC1, DE11 variable frequency drives"
DB1 variable frequency drives have no internal bus termination
resistor.
Use EASY-NT-R if necessary.
DB1 Variable Frequency Drives 09/17 MN040031EN www.eaton.com
X1
8
RJ45
RS485
L1 L2
L3
(L ) (N )
U V W

Advertisement

Table of Contents
loading

Table of Contents