When to apply a sine filter
Deciding to apply a sine filter depends upon several design
factors. The length of the cable between the drive and motor;
whether there is concern for motor heating due to additional
harmonics; the motor design (inverter duty versus non-inverter
duty), all play a role in the application decision. If the cable
length from drive to a standard motor or to an inverter duty
motor is greater than 1250 feet, apply a Sine Filter.
Sine filter ratings
The connected motor horsepower and current determine
which SC9000 EP sine filter to apply. Tables 16 and 17 show
the filter catalogue numbers along with corresponding
induction motor ratings. Contact the factory for synchronous
motor applications.

Table 16. 2400 V sine filters for induction motors

Catalog
Motor
Filter
number
power
output
39C2022
(hp)
(A)
G02
350
82
G04
450
104
G06
600
135
G08
800
178
G10
1000
223
G11
1250
279
G12
1500
335
G14
2000
446
G16
2500
558
Cabinet
Watts
size
loss
(H x W x D)
(W)
92 x 40 x 50
1492
92 x 40 x 50
1759
92 x 40 x 50
2151
92 x 40 x 50
2628
92 x 40 x 50
3142
92 x 40 x 50
3720
92 x 40 x 50
4013
92 x 40 x 50
5043
92 x 40 x 50
6327
SC9000 EP medium voltage drives IB020001EN—February 2016 www.eaton.com
Appendix D: Optional equipment

Table 17. 4160 V Sine filters for induction motors

Catalog
Motor
Filter
number
power
output
39C2022
(hp)
(A)
G22
350
47
G24
450
60
G26
600
77
G28
800
103
G30
1000
128
G31
1250
162
G32
1500
186
G34
2000
250
G36
2500
312
G38
3000
380
G39
3500
434
G40
4250
533
G41
5000
624
G42
6000
747
Cooling requirements and filter monitoring
Sine filters are power components and require cooling to
operate properly. Each sine filter cabinet is equipped with
cooling fans and inlet air filters to provide satisfactory
cooling. The sine filter reactors are also equipped with
over-temperature switches and the capacitors have
over-pressure switches to detect adverse conditions.
Maintenance
Sine Filter maintenance consists of periodic inspections of
the cooling air fans and inlet air filters, and periodic checks of
the oil-filled capacitors.
Inspect the cooling fans and inlet air filters at least once
every three months. Clean the filters with an air jet and
dust the fans to prevent dust buildup in the fan motor and
bearings. Replace fans every three to five years.
Check the capacitors annually.
Cabinet
Watts
size
loss
(H x W x D
(W)
92 x 40 x 50
1530
92 x 40 x 50
1792
92 x 40 x 50
2199
92 x 40 x 50
2708
92 x 40 x 50
3245
92 x 40 x 50
3860
92 x 40 x 50
4123
92 x 40 x 50
5204
92 x 40 x 50
6495
92 x 40 x 50
8375
92 x 40 x 50
9152
92 x 40 x 50
11315
90 x 56 x 50
13131
90 x 56 x 50
15212
69