FC Protocol
Control Word Bit Descriptions
Control
Word Bit
Descriptions
Conversion
Conversion
Factor
The different attributes for each parameter
can be seen in the section on factory settings.
Since a parameter value can only be
transferred as a whole number, a conversion
factor must be used to transfer decimals.
Example:
Example:
Example:
Example:
Example:
Parameter 201: Minimum Frequency,
conversion factor 0.1. If parameter 201 is to
be set to 10 Hz, a value of 100 must be
transferred, since a conversion factor of 0.1
means that the transferred value will be
multiplied by 0.1. A value of 100 will, therefore,
be understood as 10.0.
Memory
Parameter Values
Mapping
Standar
Standar
Standar
Standard Data T
Standar
Standard data types are int16, int32, uint8,
uint16 and uint32. They are stored as 4x
registers (40001 – 4FFFF). The parameters
are read using function 03
Registers." Parameters are written using
function 6
register (16 bits), and function 10
Multiple Registers" for 2 registers (32 bits).
Valid sizes to read are 1 register (16 bits) and
2 registers (32 bits).
MG.10.P2.22 - VLT is a registered Danfoss trademark
B it
0
0 0
P r e s e t R e f . L S B
0 1
P r e s e t R e f. M S B
0 2
D C B r a k e
0 3
C o a s t S t o p
0 4
" Q u ic k " S t o p
0 5
F r e e z e F r e q .
0 6
R a m p S t o p
0 7
n o R e s e t
0 8
n o J o g
0 9
n o f u n c t io n
1 0
D a t a N o t V a lid
1 1
R e la y 1 O F F
1 2
R e la y 2 O F F
1 3
S e t u p L S B
1 4
S e t u p M S B
1 5
n o R e v e r s in g
d Data T
d Data T
ypes
ypes
d Data Types
d Data T
ypes
ypes
"Read Holding
HEX
"Preset Single Register" for 1
HEX
1
n o D C B r a k e
n o C o a s t S t o p
n o " Q u ic k " S t o p
n o F r e e z e F r e q .
S t a r t
R e s e t
J o g
D a t a V a lid
R e la y 1 O N
R e la y 2 O N
R e v e r s in g
Nonstandar
Nonstandard Data T
Nonstandar
Nonstandar
Nonstandar
Nonstandard data types are text strings and
are stored as 4x registers (40001 – 4FFFF).
The parameters are read using function 03
"Read Holding Registers" and written using
function 10
Valid sizes to read are 1 register (2 characters)
through 10 registers (20 characters). See Text
Blocks section in this manual for truncation/
"Preset
space fill rules. IND (Modbus Register 1) must
HEX
be written with a value of 0400
0500
(write) prior to reading or writing a
HEX
text string.
Stop Commands
The precedence of the stop
commands is as follows:
1. Coast stop
2. Quick stop
3. DC Brake
4. Normal (Ramp) stop
Index
Index
Factor
Factor
Index
Index
Index
Factor
Factor
Factor
74
3.6
2
100.0
1
10.0
0
1.0
-1
0.1
-2
0.01
-3
0.001
-4
0.0001
d Data T
d Data Types
d Data T
d Data T
ypes
ypes
ypes
ypes
"Preset Multiple Registers."
HEX
HEX
HEX
(read) or
17