Table 10.2 Drive trip indications
Trip
SlotX HF
SlotX Error
SlotX Not Fitted
SlotX Different
10.3

Ethernet sub trip codes

Table 10.3 below shows the possible Ethernet sub trip codes displayed in Pr 0.10.070
and their relevant text strings.
Table 10.3 Ethernet error codes
Value
Sub trip string
Pr 0.10.070
100
Link Loss
101
E/IP Timeout
102
E/IP Read Param
103
E/IP Write Param
104
E/IP Fault
105
Modbus Timeout
106
Cyclic Timeout
107
Cyclic RX Late
108
INIT Switch
109
INIT PTP
110
INIT Cyclic
111
INIT Modbus
112
INIT SMTP
113
INIT Ethernet/IP
114
INIT TCP/IP
115
Ethernet Failure
116
E/IP PLC IDLE
117
Sync Task ORun
184
Description
The drive has detected that an Ethernet interface is present but is unable to
communicate with it due to a hardware fault.
User trip generated by the Ethernet interface
This trip will occur if a drive slot was previously configured with an option
module but on power up, no option module was detected.
This trip will occur if a drive slot was previously configured with an option
module but on power up, a different option module was detected. Replacing
the option module with another one of the same ID number will not initiate
this trip. The trip will also occur if an option module is installed to a
previously unused slot.
Description
Network link has been lost
An Ethernet/IP RPI timeout trip has occurred
Invalid read consistency parameter, is parameter read
only?
Invalid write consistency parameter, is parameter read
only?
An unexpected Ethernet/IP error has occurred
The Modbus connection has timed out
Cyclic Rx link timeout
Cyclic Rx data was received late
Ethernet switch initialization error
IEEE1588 (Precision Time Protocol) initialization error
Cyclic data initialization error
Modbus TCP initialization error
Email (SMTP) initialization error
Ethernet/IP initialization error
TCP/IP initialization error
Ethernet controller initialization error
Ethernet/IP PLC Idle
Synchronous task overrun
SI-Ethernet User Guide