S.10.055
Minimum
Default
Type
Display Format
Coding
This parameter specifies the watchdog timer for the Rx2 link. If no cyclic data is
received on the Rx2 link the action taken will be determined by the setting in Rx2
Timeout Action (S.10.056).
It is good system design to allow for some message loss by setting the timeout duration
NOTE
to be greater than the transmit period by a factor of 2 or more.
S.10.056
Minimum
Default
Type
Display Format
Coding
Value
0
1
2
Defines the action to be taken for a timeout on the Rx2 link.
S.10.057
Minimum
Default
Type
Display Format
Coding
Value
0
1
2
3
4
This parameter defines the slot in which an event will occur if a cyclic data timeout
occurs on the Rx2 link.
70
Rx2 Timeout
0
100
16 Bit User Save Update Rate
None
RW, BU
Rx2 Timeout Action
0
0
8 Bit User save
None
RW, TE, BU
Text
Trip
Trip drive with Slx.Er and sub-trip code 106 (Cyclic Timeout)
Clear output PLC output parameters will have their values set to zero
Hold last
Hold the last value in output parameters
Rx2 Timeout Event Destination
0
0
8 Bit User save
None
RW, TE, BU
Text
This slot
Slot 1
Slot 2
Slot 3
Slot 4
Maximum
Units
Decimal Places
Maximum
Units
Update Rate
Decimal Places
Description
Maximum
Units
Update Rate
Decimal Places
Description
Trigger module event in this slot
Trigger module event in slot 1
Trigger module event in slot 2
Trigger module event in slot 3
Trigger module event in slot 4
65535
ms
Read on reset
0
2
Read on reset
0
4
Read on reset
0
SI-Ethernet User Guide