S.02.005
Minimum
Default
Type
Display Format
Coding
Controls whether or not the module will attempt to use a Dynamic Host Configuration
Protocol (DHCP) server to obtain the IP address, subnet mask, default gateway and
DNS servers.
When DHCP is enabled, the following parameters will become read-only immediately
(no reset required):
IP Address (S.02.006)
Subnet Mask (S.02.007)
Default Gateway (S.02.008)
Primary DNS (S.02.009)
Secondary DNS (S.02.010)
S.02.006
Minimum
Default
Type
Display Format IP Address
Coding
Controls and displays the IP address of the module.
If DHCP is enabled this parameter becomes read-only, and until an IP address is
allocated to the module will display 0.0.0.0.
If DHCP is disabled the module will initialize, on reset or power cycle, with the IP
address stored for the parameter.
SI-Ethernet User Guide
Issue: 1
DHCP Enable
0
1
1 Bit User Save
None
RW, BU
IP Address
0
(Display: 0.0.0.0)
3232235876
(Display:192.168.1.100)
32 Bit User Save
RW, BU
Maximum
1
Units
Update Rate
Background read
Decimal Places
0
4294967295
Maximum
(Display:255.255.255.255)
Units
DHCP enabled: write on
event;
Update Rate
DHCP disabled: read on
reset
Decimal Places 0