Emerson Unidrive M700 User Manual page 128

Si-ethernet and unidrive m - onboard ethernet
Hide thumbs Also See for Unidrive M700:
Table of Contents

Advertisement

Example
To write the value 12345 to drive parameters 0.20.021 through 0.20.023 and read the
values of parameters 0.20.024 through 0.20.026 (Transaction ID=42) using standard
addressing:
Master request data
Hex
Description
Byte
value
Transaction ID
0-1
00 2A
(42)
Protocol ID
2-3
00 00
(0=TCP/IP)
Length
4-5
00 17
(Bytes=6)
Unit identifier
6
FF
(FF= Drive)
Function code
7
17
(23)
Start read register
8-9
47 E7
(20.023)
Number of read registers
10-11
00 06
(6)
Start write register
12-13
47 E4
(20.020)
Number of write registers
14-15
00 06
(6)
Length of register data to
16
0C
write
(Bytes=12)
00 00
Register data 0
17-20
30 39
(12345)
00 00
Register data 1
21-24
30 39
(12345)
00 00
Register data 2
25-28
30 39
(12345)
128
Slave response data
Hex
Byte
Description
value
Transaction ID
0-1
00 2A
(42)
Protocol ID
2-3
00 00
(0=TCP/IP)
Length
4-5
00 0F
(Bytes=15)
Unit identifier
6
FF
(FF= Drive)
Function code
7
17
(23)
Length of data
8
0C
(Bytes=12)
?? ??
Register data 0
9-12
?? ??
(Pr 20.024)
?? ??
Register data 1
13-16
?? ??
(Pr 20.025)
?? ??
Register data 2
17-20
?? ??
(Pr 20.026)
SI-Ethernet User Guide
Issue: 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents