Diagnostics; Trip Indications; Table 13-1 Trip Indications - Emerson Quantum MP QMP45A4 User Manual

Table of Contents

Advertisement

Safety
Product
Mechanical
Information
Information
Installation
13

Diagnostics

The display on the drive gives various information about the status of the
drive. These fall into three categories:

Trip indications

Alarm indications
Status indications
Users must not attempt to repair a drive if it is faulty, nor
carry out fault diagnosis other than through the use of the
diagnostic features described in this chapter.
If a drive is faulty, it must be returned to an authorized
WARNING
Control Techniques distributor for repair.
13.1
Trip indications
If the drive trips, the output of the drive is disabled so that the drive stops
controlling the motor. The upper display indicates that a trip has
occurred and the lower display shows the trip.
Trips are listed alphabetically in Table 13-1 based on the trip indication
shown on the drive display. Refer to Figure 13-1.
If a display is not used, the drive LED Status indicator will flash if the
drive has tripped. Refer to Figure 13-2.
The trip indication can be read in Pr 10.20 providing a trip number. Trip
numbers are listed in numerical order in Table 13-2 so the trip indication
can be cross referenced and then diagnosed using Table 13-1.
Example
1. Trip code 3 is read from Pr 10.20 via serial communications.
2. Checking Table 13-2 shows Trip 3 is an AOC trip.
Comms
No.
code
3
3. Look up AOC in Table 13-1.
4. Perform checks detailed under Diagnosis.
13.2
Trip indications

Table 13-1 Trip indications

Trip
AOC
Instantaneous output over current detected: Peak current greater than 225%
Check for short circuit on armature cabling
3
Check integrity of motor insulation
Check current loop stability
AOP
Voltage has been applied to the armature but no current feedback has been detected
Check the armature circuit
158
C.Acc
SMARTCARD trip: SMARTCARD Read / Write fail
Check SMARTCARD is installed / located correctly
185
Ensure SMARTCARD is not writing data to data location 500 to 999
Replace SMARTCARD
SMARTCARD trip: The menu 0 parameter modification cannot be saved to the SMARTCARD because the necessary file has
C.boot
not been created on the SMARTCARD
A write to a menu 0 parameter has been initiated via the keypad with Pr 11.42 (SE09, 0.30) set to auto(3) or boot(4), but the
necessary file on the SMARTCARD has not bee created
177
Ensure that Pr 11.42 (SE09, 0.30) is correctly set and reset the drive to create the necessary file on the SMARTCARD
Re-attempt the parameter write to the menu 0 parameter
C.bUSY
SMARTCARD trip: SMARTCARD can not perform the required function as it is being accessed by a Solutions Module
178
Wait for the Solutions Module to finish accessing the SMARTCARD and then re-attempt the required function
C.Chg
SMARTCARD trip: Data location already contains data
Erase data in data location
179
Write data to an alternative data location
Quantum MP User Guide
Issue: A3
Electrical
Getting
Basic
Installation
Started
parameters
Keypad
Trip
display
AOC
www.emersonct.com
Running
SMARTCARD
Optimization
the Motor
Operation
Figure 13-1 Keypad status modes
Healthy Status
Figure 13-2 Location of the status LED
Non flashing:
Normal status
Diagnosis
Onboard
Advanced
Technical
Diagnostics
PLC
Parameters
Data
Status Mode
Alarm Status
Trip Status
Flashing:
Trip status
UL
Information
Drive status
= tripped
Trip type (UU
= undervolts)
157