Standard Run 3 Wire Connection - Baldor ID15J1F50-ER Installation And Operating Manual

Inverter control. 15j series
Table of Contents

Advertisement

Standard Run 3 Wire Connection

Figure 3-11 Standard Run 3-Wire Connection Diagram
Function
ANA CMD Select
Preset Speed 1
Preset Speed 2
Preset Speed 3
J4-11
Momentary CLOSED starts Forward motor rotation.
J4-12
Momentary CLOSED starts Reverse motor rotation.
J4-13
Momentary OPEN motor decels to stop (depending on Keypad Stop mode).
J4-14
OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J4-15
Selects preset speeds as defined in Table 3-7.
J4-16
Selects preset speeds as defined in Table 3-7.
J4-17
If J4-17 is connected, you must set Level 2 Protection block, External Trip to
"ON" to activate the opto input.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
CLOSED allows normal operation.
MN715J
Table 3-7 Speed Select
Speed Select 1
Open
Closed
Closed
Open
Speed Select 2
Open
Open
Closed
Closed
Receiving and Installation 3-17