Customer Interface And Dry Ports (Volt-Free Contacts) - ABB Conceptpower DPA 500 User Manual

Ups system 100 - 500 kw
Hide thumbs Also See for Conceptpower DPA 500:
Table of Contents

Advertisement

5.1.2

Customer interface and DRY PORTs (volt-free contacts)

All Terminals X1-X3 can hold Cable from 0.2mm2 – 1.5mm2
X1 is a 230VAC output which allows to interface with a interlock system.
All X2 are potential free contacts and are rated: Max 250Vac/8A; 30Vdc/8A; 220Vdc/0.12A
All X3 (except X3 5/6 which is a 12VDC source) are inputs, cable max. R 50Ω at 20mA
Block
Terminal
Contact
X3 / 14
X3 / 13
X3 / 12
X3 / 11
X3 / 10
X3 / 9
X3 / 8
X3 / 7
X3
X3 / 6
X3 / 5
X3 / 4
X3 / 3
X3 / 2
X3 / 1
X2 / 18
X2 / 17
X2 / 16
X2 / 15
X2 / 14
X2 / 13
X2 / 12
X2 / 11
X2 / 10
X2
X2 / 9
X2 / 8
X2 / 7
X2 / 6
X2 / 5
X2 / 4
X2 / 3
X2 / 2
X2 / 1
X1 / 2
X1
X1 / 1
Table 11: Customer Interface Conceptpower DPA 500
GND
IN
GND
IN
GND
IN
GND
IN
12V
GND
GND
IN
C
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
2AT
04-3275_OPM_ABB_CONCEPTPOWER_DPA_500kW_EN_REV-A.docx
Signal
On Display
GND
-
+3.3VDC
-
GND
GENERATOR_
OPER_ON
+12Vdc
GND
PARRALEL_SW_OPEN
PARRALEL_SW_CLOSE
+12Vdc
GND
EXT_MAN_BYP
+12Vdc
+12Vdc
-
GND
-
GND
REMOTE_
SHUTDOWN-
+12Vdc
-
REMOTE_
SHUTDOWN-
-
-
-
-
-
-
-
COMMON_ALARM
ALARM
LOAD_ON_MAINS
Message
BATT_LOW
ALARM
LOAD_ON_INV
Message
MAINS_OK
ALARM
-
-
EXT_MAN_BYP
Modifications reserved
Function
Battery Temperature
(only the optional battery sensor from ABB is
compatible)
Generator Operation
(N.O.) Min. contact load 12V / 1mA
External Output Breaker
(N.O.) Min. contact load 12V / 20mA.
External Manual Bypass (Ext. IA1)
(N.O.) Min. contact load 20mA
+ 12 VDC source (UPS protected)
(Max. 200mA)
RSD (Remote Shut down)
Default setting: disabled. Possibility to
enable and set NO or NC via NewSet.
RSD (Remote Shut down ) for
external switch
Max. 250Vac/8A ;30Vdc/8A ;110Vdc/0.3A
;220Vdc/0.12A
Common
Relais AUX
(function on request, to be defined)
Common
No Alarm Condition
Common Alarm (System)
Common
No Load on Bypass
Load On Bypass (Mains)
Common
Battery Ok
Battery Low
Common
No Load on Inverter
Load on Inverter
Common
Mains Failure
Mains Present
Interlock Function
Max. 30Vdc/2A; 60Vdc/0.7A
(Ext Manual Bypass) / 2AT
Page 27/78 ABB