Customer interface and DRY PORTs (volt-free contacts)

All Terminals X1-X3 can hold Cable from 0.2mm2 – 1.5mm2
X1 is a 230VAC output which allows to interface with a interlock system.
All X2 are potential free contacts and are rated: Max 250Vac/8A; 30Vdc/8A; 220Vdc/0.12A
All X3 (except X3 5/6 which is a 12VDC source) are inputs, cable max. R 50Ω at 20mA
Table 10: Customer Interface Conceptpower DPA 500
Block
Terminal
Contact
X3 / 14
GND
IN
X3 / 13
X3 / 12
GND
IN
X3 / 11
X3 / 10
GND
IN
X3 / 9
X3 / 8
GND
IN
X3 / 7
X3
X3 / 6
X3 / 5
X3 / 4
GND
IN
X3 / 3
X3 / 2
C
NO
X3 / 1
X2 / 18
C
NC
X2 / 17
NO
X2 / 16
X2 / 15
C
NC
X2 / 14
NO
X2 / 13
X2 / 12
C
NC
X2 / 11
NO
X2 / 10
X2
X2 / 9
C
NC
X2 / 8
NO
X2 / 7
X2 / 6
C
NC
X2 / 5
NO
X2 / 4
X2 / 3
C
NC
X2 / 2
NO
X2 / 1
X1 / 2
X1
X1 / 1
Modifications reserved
Page 32/94
Signal
GND
+3.3VDC
GND
+12Vdc
GND
PARRALEL_SW_OPEN
PARRALEL_SW_CLOSE
+12Vdc
GND
+12Vdc
+12Vdc
12V
GND
GND
GND
+12Vdc
-
-
-
-
-
ALARM
Message
ALARM
Message
ALARM
-
2AT
-
On Display
Function
Battery Temperature
-
(only the optional battery sensor from
-
ABB is compatible)
Generator Operation
GENERATOR_
OPER_ON
(N.O.) Min. contact load 12V / 1mA
External Output Breaker
(N.O.) Min. contact load 12V / 20mA.
External Manual Bypass (Ext.
EXT_MAN_BYP
IA1)
(N.O.) Min. contact load 20mA
+ 12 VDC source (UPS
-
protected)
-
(Max. 200mA)
RSD (Remote Shut down)
REMOTE_
Default setting: disabled. Possibility to
SHUTDOWN-
enable and set NO or NC via NewSet.
RSD (Remote Shut down ) for
external switch
REMOTE_
SHUTDOWN-
Max. 250Vac/8A ;30Vdc/8A
;110Vdc/0.3A ;220Vdc/0.12A
Common
-
Relais AUX
-
(function on request, to be defined)
-
Common
COMMON_ALARM
No Alarm Condition
Common Alarm (System)
Common
LOAD_ON_MAINS
No Load on Bypass
Load On Bypass (Mains)
Common
BATT_LOW
Battery Ok
Battery Low
Common
LOAD_ON_INV
No Load on Inverter
Load on Inverter
Common
MAINS_OK
Mains Failure
Mains Present
Interlock Function
EXT_MAN_BYP
Max. 30Vdc/2A; 60Vdc/0.7A
(Ext Manual Bypass) / 2AT