6 C O M M U N I C AT I O N

6 .4 Output Dry Contact Port

6 .4 .1 Dry IN

6.4.1-1:
Dry in allows a remote action to switch on/
Dry IN
switch off/ maintenance bypass the UPS.
6.4.2-1:
This is done by switching the contact from

Dry OUT

Opened to close.
6.4.1-1

6 .5 Network management card (optional)

The PowerValue 11 RT G2 5–10 kVA UL is equipped
with an intelligent slot for optional cards for
remote management of the UPS through the
Internet/ Intranet. Either of the following
accessories can be installed in the intelligent slot:
• SNMP/Modbus Card – SNMP/Modbus, HTTP
and monitoring capabilities through a Web
browser interface.
• AS400 Card – AS400 card for AS400
communication protocol.
6 .5 .1 Installing a serial network management
card (optional)
Each UPS has a communication slot for an
optional serial network management protocol
(SNMP/Modbus) card. After installing an SNMP/
Modbus card, an environmental monitoring probe
can be connected.
NOTE


THE UPS DOES NOT HAVE TO BE SHUT
DOWN BEFORE INSTALLING A
COMMUNICATION CARD.
s h u a i q i _ h e
s h u a i q i _ h e
s h u a i q i _ h e 2 0 2 2 - 0 2 - 1 5
s h u a i q i _ h e
2 0 2 2 - 0 2 - 1 5
2 0 2 2 - 0 2 - 1 5
2 0 2 2 - 0 2 - 1 5
6 .4 .2 Dry OUT
The dry out port is normally open. If the dry out
port is close, it indicates that the UPS is running
in summary alarm / on battery / battery low /
UPS ok / on bypass.


6.4.2-1
To install a network management card:
1. Remove the two screws that protect
the communication slot of the UPS.
2. Insert the SNMP/Modbus card into
the communication slot.
3. Screw the SNMP/Modbus card onto the slot
using the screws removed in Step 1
For more information on the SNMP/Modbus
Cards, see the SNMP/Modbus user's manual.

6 .5 .2 Monitoring software

The UPS can be monitored using software. The
software provides a remote and safe shutdown
for multi-client systems in case of absence of
power at the UPS output. Instructions on how to
install the software are provided with the
network management cards.