POWERVALUE 11 RT G2 IN — 1-3 KVA
—
5. Battery replacement
WARNING!
Please read the following instructions to perform
a correct battery replacement:
1. Remove the front panel.
—
5-1
Front panel removal
2. Disconnect the battery plug.
—
5-2
Battery plug disconnection
3. Take off the front battery cover by removing
the 4 screws.
—
5-3
Battery cover removal
4. Extract the battery tray from the UPS and
replace the batteries.
Please refer to chapter 2 for safety
instructions.
2
1
5. Reinsert the battery tray with the replaced
batteries back into the original location
5-4
Batteries replacement
6. Tightly secure the 4 screws to lock back the
battery cover to the unit.
5-5
Battery cover insertion
7. Reconnect the battery plug.
—
5-6
Battery plug connection
8. Reassemble the front panel back to conclude
the battery replacement.
1
2
—
5-7
Front panel insertion
—