Installation And Wiring; Positioning Of The Ups And Battery Cabinet - ABB PowerWave 33 Series 3 User Manual

60 – 120 kw
Table of Contents

Advertisement

4 Installation and wiring

4.1 Positioning of the UPS and battery cabinet

The UPS is designed for location in a restricted access location only and should be located where:
The relative humidity does not exceed 95% (non-condensing) and the temperature remains always
between 0°C and +40°C. Note: an optimal temperature for the UPS and especially for VRLA
batteries is 20°C- 25°C. The UPS room shall have temperature control (air-cooling)
Any kind of dust or corrosive/explosive gases must be absent
Fire protection standards are respected
The place is vibration free
The floor material should be non-flammable and strong enough to support the heavy load.
Cabling can be performed easily
Available front accessibility of 1m from front of the unit for service or maintenance
Only front access is necessary for service and maintenance
If the UPS will be installed in bayed enclosures, partition walls have to be installed as well
Also the needed clearances to allow proper airflow on the UPS system and to allow proper service and
maintenance shall be respected as reported in the Table 4 below.
Modifications reserved
Page 14/50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents