Battery Characteristics; Output Characteristics - ABB CONCEPTPOWER CLASSIC DPA-50 User Manual

Conceptpower dpa series
Table of Contents

Advertisement

10.4 BATTERY CHARACTERISTICS

Module Range
Module Type
Variable Number of 12V Battery Blocks
Maximum Battery Charger Current
Battery Charging Curve
Temperature compensation
Battery Test
Battery Type

10.5 OUTPUT CHARACTERISTICS

Module Range
Module Type
Output Rated Power per Module
Output Rated Power per Module
Output Current In @ cosphi 1.0 (400 V)
Output Rated Voltage
Output Voltage Stability
Output Voltage Distortion
Output Frequency
Output Frequency Tolerance
Bypass operation
Permissible Unbalanced Load
(All 3 phases regulated independently)
Phase Angle Tolerance
(With 100 % Unbalanced load)
Overload Capability on Inverter
Output short capability (RMS)
Crest - Factor
DPA 30S2
No.
40-50
A
DPA 30 S2
kVA
30
KW
24
A
35
V
Static:
%
Dynamic (Step load 0%-100% or 100%-0%)
With Linear Load
%
With Non-linear Load
(EN62040-3)
Hz
Synchronized with mains
%
(selectable for bypass operation)
Free running
At Nominal Input voltage of 3x400 V +/- 15%
or 196 V to 264 V ph-N
%
100%
Deg.
± 0 deg.
125 % load
%
150 % load
Inverter :
A
Bypass :
04-3008_S10_ABB_TDSCPDPA-S2_GB_121202
Printed in Switzerland – Modifications reserved
MX
DPA 40 S2
40-50
10A (15A on request)
Ripple free ; IU (DIN 41773)
Standard (temp. sensor optional)
Automatic and periodically (adjustable)
Maintenance free VRLA or NiCd
MX
DPA 40 S2
40
32
46.5
3x380/220V or 3x400/230V or 3x415/240V
50 Hz or 60 Hz
up to 3 x In during
10 x In during
3 : 1
Section-10
DPA 50 S2
40-50
DPA 50 S2
50
40
58
< ± 1%
< ± 4%
< 2%
< 4%
< ± 2 %
or < ± 4 %
± 0.1 %
10 min.
60 sec.
40 ms
10 ms
Page 7/19 ABB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents