Battery Characteristics; User Interface - Communication; System Display - ABB Conceptpower DPA 500 User Manual

480v ul – modular ups, 100kw – 3 mw
Hide thumbs Also See for Conceptpower DPA 500:
Table of Contents

Advertisement

11.4 Battery Characteristics

Battery Characteristics
Technology: VRLA, vented lead-acid, NiCd
Battery/DC Nominal Input
Number of 12 V blocks
Number of 1.2 V NiCd cells (even and odd)
Battery charger - each module has its own decentralized charger
Max. current charger capability
Max. power charger capability
Floating voltage (VRLA / NiCd)
End of discharge voltage (VRLA / NiCd)
r.m.s. ripple current (percentage of the battery capacity )
Temperature compensation: optional
Battery test: automatic and periodic battery test (selectable)
1)
IMPORTANT NOTES:
- At output voltage 480VAC, the minimum number of 12V blocks is 45.
11.5 User Interface – Communication

System Display

DPA display (or module display)
MIMIC diagram
RS232 on Sub-D9 port
RS232 on USB port
User Interfaces : Inputs
DRY PORT
User Interfaces : Outputs
DRY PORT
RS485 on RJ45 port
RS485 on RJ45 port
Slot for SNMP
11.5.1 System Display
The user-friendly touchscreen graphical display on the system level offers the opportunity of directly monitoring the system status as well
as the status of each individual module. The graphical display additionally provides all the measurements (module and system level) and
the user is able to transfer from INVERTER to BYPASS and vice-versa. All other commands must be performed on the DPA display. With
both displays in place (module and system level), the UPS offers full user friendliness without making compromises on robustness.
7" touchscreen display (one per cabinet)
2 x 20 character LCD display (one per module)
LED-indicator, 5x green/red LEDS (one per module)
For monitoring and integration in network management
1 Remote Shut down [EMERGENCY OFF (Normally closed)]
1 GEN-ON (Normally open)
1 Programmable User's Inputs (Normally open)
1 Temp. Sensor for Battery Control
6 voltage free contacts
For remote signaling and automatic computer shutdown
Remote monitoring system with remote panel (graphical display)
For multidrop purpose
SNMP card
For monitoring and integration in network management
Values
Unit
540V (nom)
45
450
60
A
30
kW
2.25 / 1.40
VDC
1.68 / 1.05
2
%
Conceptpower DPA 500 480V UL │94-12-043275 A02 61
Optional
Optional