Horizontal Venting - kozy heat CALLAWAY 50 Installation And Operation Manual

Direct vent gas fireplace
Hide thumbs Also See for CALLAWAY 50:
Table of Contents

Advertisement

7.5.1.2 Horizontal Venting

IMPORTANT: Horizontal vent sections require ¼ in (6 mm) rise for every
12 in (305 mm) of travel.
IMPORTANT: The horizontal vent heat shield MUST BE INSTALLED
when using a 45° elbow off the back of the appliance. See Section 7.7
on page 28.
Table 7.2, Natural Gas and Propane Minimum/Maximum Horizontal
Terminations (no vertical venting)
Minimum Horizontal
Minimum
Venting
Horizontal Run
45° elbow
Minimum/ Maximum Horizontal Terminations:
45° horizontal elbow + 6" (152mm) minimum horizontal / 24"
(609mm) maximum horizontal + termination cap
Figure 7.2, Combination Venting
24 VENTING
Maximum
Horizontal Run
6 in
152 mm
24 in
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
DIAG.2 NATURAL GAS AND PROPANE HORIZONTAL VENTING
(A) Stand-off Heat Shields
(B) 45° Elbow
(C) 90° Elbow (not applicable)
B
A
609 mm
(D) Termination Cap
24"
(609mm)
6"
(152mm)
#CLW-50 R.1 March 2018
D